Data
Centers within Corporate Headquarters – LEED
Gold
New York
(Financial Services Client)
Tier III
2.4 Million SF
Raised Floor: 40,000 SF
Density: 100 W / SF
Redundancy: N+1
Chiller Plant: 400-Ton Modular Electric Chiller
Diesel Generator Quantity & Capacity: (5) N+1 / 2,250
kW
UPS System: (1) N+1 / 750 kVA
Services Provided: MEP/FP Engineering & Commissioning
Data Center Expansion
North Carolina
(Luxury Retailer)
Tier III
20,000 SF
Raised Floor: 10,000 SF
Density: 90 W / SF
Redundancy: 2N
Chiller Plant: Air Cooled Condensers
Diesel Generator Quantity & Capacity: (4) N+1 / 1,500
kW
UPS System: (2) 2N / 625 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center
Florida
(Financial Services Client)
Tier III
125,000 SF
Raised Floor: 10,000 SF
Density: 100 W / SF
Redundancy: N+1
Chiller Plant: 350-Ton Modular Chiller Plant
Diesel Generator Quantity & Capacity: N+1 / 4,000kW
UPS System: N+1, 1500 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center
Korea
(Global Business and Computer/IT Services Client)
Tier IV
100,000 SF
Raised Floor: 50,000 SF
Density: 100 W / SF
Redundancy: 2(N+1)
Chiller Plant: (4) N+2 450-Ton Expandable to (10) N+2 450-Ton
Diesel Generator Quantity & Capacity: (5) N+1 / 2250
kW Expandable to (9) N+1 / 2250 kW
UPS System: 6 - (4) 800 kW
Services Provided: MEP/FP Engineering
Data Center UPS Upgrade
New Jersey
(Pharmaceutical Manufacturing Client)
Tier III
Raised Floor: 30,000 SF
Density: 60 W / SF
Redundancy: N+1
UPS System: Increased the Capacity of 2 UPS to 1,200 kW
Services Provided: MEP/FP Engineering
Data Center Infrastructure
Upgrades
New York
(Global Business and Computer/IT Services Client)
Tier III
350,000 SF
Raised Floor: 160,000 SF
Density: 50 W / SF
Redundancy: 2N
Chiller Plant: (4) N+1 3,600-Ton
Diesel Generator Quantity & Capacity: (10) N+1 / 2.5
MW Plant
UPS System: (1) 2N 2,700 kW
Services Provided: MEP/FP Engineering & Commissioning
Data Center Generator Plant
New York
(Financial Services Client)
Tier III
700,000 SF
Raised Floor: 15,000 SF
Density: 100 W / SF
Redundancy: 2N
Diesel Generator Quantity & Capacity: (4) 2,800 kW
UPS System: 2N / 1,500 kVA
Services Provided: MEP/FP Engineering & Commissioning
Data
Center Electrical Systems Upgrade
New Jersey
(Financial Services Client)
Diesel Generator Quantity & Capacity: 15.6 MW Kerosene
Turbine Generator
Services Provided: MEP/FP Engineering & Commissioning
Data Center UPS Upgrade
New York
(Financial Services Client)
Tier II
25,000 SF
Density: 100 W / SF
Redundancy: 2N (UPS Only)
UPS System: (2) 2N/150 kVA
Services Provided: MEP/FP Engineering
Data Center Generator Upgrade
New York
(Global Business and Computer/IT Services Client)
Redundancy: N+1
Diesel Generator Quantity & Capacity: (3) N+1 / 2.5
MW
Services Provided: MEP/FP Engineering & Commissioning
New Data Center
New Jersey
(Financial Services Client)
Tier IV
112,000F
Raised Floor: 50,000 SF
Density: 150 W / SF
Redundancy: 2N
Chiller Plant: (1) 2N 3,600-Ton
Diesel Generator Quantity & Capacity: (7) N+1 / 2,800
kW
UPS System: 7.5 MW
Services Provided: Commissioning
Data Center Generator Upgrade
New Jersey
(Financial Services Client)
Tier IV
Redundancy: 2N
Diesel Generator Quantity & Capacity: (1) 2,000 kW
Services Provided: Commissioning
New Data Center
New Jersey
(Financial Services Client)
Tier III
100,000F
Raised Floor: 50,000 SF
Density: 150 W / SF
Redundancy: N+1
Chiller Plant: (4) N+1 470-Ton, (2) N+1 750-Ton Water-Cooled
Chillers
Diesel Generator Quantity & Capacity: (4) N+1 / 2,200
kW
UPS System: (1) 2N UPS and UPS Distribution Systems
Services Provided: Commissioning
New Data Center
Georgia
(Financial Services Client)
Tier IV
185,000 SF
Raised Floor: 40,000 SF
Density: 40 W / SF
Redundancy: 2N
Chiller Plant: (2) 2N 950-Ton
Diesel Generator Quantity & Capacity: (3) 2,000 kW
UPS System: 2N / 2,025 kW
Services Provided: Commissioning
New Data Center
South Dakota
(Financial Services Client)
Tier IV
185,000 SF
Raised Floor: 40,000 SF
Density: 40 W / SF
Redundancy: 2N
Chiller Plant: (2) 2N 950-Ton
Diesel Generator Quantity & Capacity: (3) 2,000 kW
UPS System: 2N / 2,025 kW
Services Provided: Commissioning
New Data Center
Illinois
(Financial Services Client)
Tier III
160,200 SF
Raised Floor: 40,000 SF
Density: 150 W / SF
Redundancy: 2N
Chiller Plant: (2) 2N 1,300-Ton
Diesel Generator Quantity & Capacity: (5) N+1 / 2,000
kW
UPS System: (2) 750 kVA
Services Provided: Commissioning
New Data Center within New
Corporate Headquarters/Trading Pavilion
North Carolina
(Financial Services Client)
Tier IV
180,000 sf
Raised Floor: 40,000 SF
Density: 70 W / SF
Redundancy: 2N
Chiller Plant: Multiple Cooling Plants Utilizing Water and
Air Cooled Chillers
Diesel Generator Quantity & Capacity: (4) N+1 / 1750
kW
UPS System: 2 (N+1) (2) 500 Kva
Services Provided: MEP/FP Engineering & Commissioning
New Data Center within New
Corporate Headquarters
Connecticut
(Financial Services Client)
Tier IV
Raised Floor: 50,000 SF
Redundancy: 2N
Chiller Plant: 3,000-Ton
Diesel Generator Quantity & Capacity: (5) N+1 / 1750
kW
UPS System: (2) 2N / 2,800 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center within Corporate
Headquarters Fit-Out
New Jersey
(Financial Services Client)
Tier IV
180,000 SF
Raised Floor: 25,000 SF
Redundancy: 2N
Chiller Plant: (4) 150-Ton Air-Cooled Chillers
Diesel Generator Quantity & Capacity: (3) 2,000 kW
UPS System: (2) 1,500 kVA
Services Provided: MEP/FP Engineering
New Data Center within Corporate
Headquarters Fit-Out
New York
(Financial Services Client)
Tier III
320,000 SF
Raised Floor: 50,000 SF
Redundancy: N + 1
Chiller Plant: (1) 500-Ton Supplemental Cooling Tower
Diesel Generator Quantity & Capacity: (1) 1,500 kW
UPS System: (1) 625 kVA
Services Provided: MEP/FP Engineering
New Data Center within New
Corporate Headquarters
New York
(Financial Services Client)
Tier III
900,000 SF
Raised Floor: 25,000 SF
Density: 40 W / SF
Redundancy: N + 1
Chiller Plant: 1,000-Ton Air-Cooled
Diesel Generator Quantity & Capacity: (1) N+1 / 4 MW
UPS System: (3) N / 1000 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center within Corporate
Headquarters Fit-Out
New York
(Financial Services Client)
Tier III
60,000 SF
Raised Floor: 15,000 SF
Density: 40 W / SF
Redundancy: 2N
UPS System: (2) 500 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center within Corporate
Headquarters Fit-Out
New Jersey
(Insurance Services Client)
Tier II
400,000 SF
Raised Floor: 35,000 SF
Redundancy: N+1
Chiller Plant: (3) 150-Ton Air-Cooled Chiller Plant
Diesel Generator Quantity & Capacity: (1) 1,500 kW
UPS System: (1) N+1 / 800 kVA
Services Provided: MEP/FP Engineering
New Data Center within a Trading
Installation
New York
(Stock Exchange)
Tier II
170,000 SF
Raised Floor: 10,000 SF
Redundancy: N+1
Chiller Plant (1) 600-Ton Cooling Tower
Diesel Generator Quantity & Capacity: (2) 1,500 kW
UPS System: (1) N+1 / 400 kVA
Services Provided: MEP/FP Engineering & Commissioning
New Data Center within Corporate
Headquarters Fit-Out
New York
(Financial Services Client)
Tier III
700,000 SF
Raised Floor: 25,000 SF
Redundancy: N+1
Chiller Plant: (2) 1,000-Ton Dry Cooler
Diesel Generator Quantity & Capacity: (3) N+1 / 2,000
kW (HITEC Units)
UPS System: Power Derived from HITEC Units
Services Provided: Commissioning
New Data Center within Headquarters
Fit-Out
New York
(Financial Services Client)
Tier III
40,000 SF
Raised Floor: 15,000 SF
Redundancy: N+1
Diesel Generator Quantity & Capacity: (1) N+1 / 800
kW
UPS System: (1) N+1 / 375 kVA
Services Provided: MEP/FP Engineering
New Data Center within Headquarters
Fit-Out
New York
(Financial Services Client)
Tier II
160,000 SF
Redundancy: N+1
Chiller Plant: (1) 2,400-Ton Refrigerant Plant, (1) 500-Ton
Additional Supplemental Condenser Water Plant
Diesel Generator Quantity & Capacity: (3) 1,500 kW
UPS System: (1) 2,000 kVA
Services Provided: MEP/FP Engineering